The EVC600i Voltage Regulator is thyristor base to control the DC exciter field power of conventional 50 or 60 Hz brushless generators. The AVR circuitry includes under speed and over load protection features. Excitation power is derived directly from the generator terminals.
Operating Temperature = -30 to 80°C (-22 to 176°F) Storage Temperature = -40 to 80°C (-40 to 176°F) Altitude = Less than 2600 meter Relative Humidity = TECHNICAL SPECIFICATION : Sensing Input : Terminal V -V for 220 Vac Terminal V -V for 400 Vac
Power Input : Voltage = 180 to 250 Vac Frequency = 50 Hz or 60 Hz
Voltage Adjust Range : 180 - 300 Vac, 300 - 520 Vac
Field Resistance : Recommend 9 - 24 Ω
Voltage Regulation = < 1%
Output Voltage : Maximum 90 Vdc @ 220 Vac
Automatic Voltage Regulator Output Current : Maximum continuous = 8 A @ 220 Vac 10 second forcing = 10 A @ 220 Vac
Paralleling : Internal burden and adjustment for 0 to 10% droop at 5 A, 0.8 PF, (from external CT)
Voltage Buildup : 4Vac, 30 Hz
External Volts Adjustment : At least 10% with 100k ohm 1 watt trimmer
Thermal Drift : 0.05% per Degree C change in AVR ambient
Analog Voltage Input : ±5VDC, adjustable output voltage is no less than 2% for 1VDC (i.e. for ±5VDC it come out to be ±10%)
Current Compensation : In = 5A Input At least 10 % @ P.F. = 0.8
Dimensions : 175 mm L x 129 mm W x 37.5 mm H