Download Tokopedia App
Tentang TokopediaMulai Berjualan PromoTokopedia Care
tokopedia-logo
Atur jumlah dan catatan

Stok Total: Sisa 5

Subtotal

Rp123.456

MEGGER SVERKER 900-CR19092 RELAY AND SUBSTATION TEST SYSTEM

Rp123.456
  • Kondisi: Baru
  • Waktu Preorder: 30 Hari
  • Min. Pemesanan: 1 Buah
  • Etalase: MEGGER
SPECIFICATIONS SVERKER 900
(Include Flight case with wheels)
Specifications are valid for resistive load, at 170-240 voltage supply
and ambient temperature +25°C ±3°C, (77°F ±5.4°F) after 30 min-
utes warm up time and in the frequency range 15 Hz to 70 Hz.
All hardware data are for full scale values.
Specifications are subject to change without notice.
Environment
Application field For use in high-voltage substations and
industrial environments.
Temperature
Operating 0°C to +50°C (32°F to +122°F)
Storage & transport -40°C to +70°C (-40°F to +158°F)
Humidity 5% – 95% RH, non-condensing
Altitude (operational) 2000 m (6500 ft)
CE-marking
LVD 2014/35/EU
EMC 2014/30/EU
RoHS 2011/65/EU
Classifications and standards
Shock and vibration IEC 60068-2-27
Vibration IEC 60068-2-6
Voltage frequency
ramp
IEC 60255-181:2019
General
Mains input 100 - 240 V AC, 50 / 60 Hz
Current consumption 10 A (max)
Power consumption 1800 VA (max)
Dimensions
Instrument 350 x 270 x 220 mm (13.8” x 10.6” x 8.7”)
Flight case with
wheels
615 x 295 x 500 mm (24.2” x 11.6” x 19.7”)
Flight case 620 x 295 x 365 mm (24.4” x 11.6” x 14.4”)
Weight 15.2 kg (33.5 lbs) Instrument only
29.2 kg (64.4 lbs) with accessories and
flight case (with wheels, GD-00185)
24.1 kg (53.1 lbs) with accessories and
flight case (GD-00182)
Display 5.7” LCD Touch screen
Available languages Czech, English, French, German, Spanish,
Swedish
Measurement section
BINARY INPUTS 1, 2, 3 ,4 and EXTERNAL TIMER
Start/Stop
Number 6
Type Dry or wet contacts max, 240 V AC or
340 V DC
Galvanic Isolation Galvanically separated
Max measuring time 35 minutes
Debounce filter Settable, 0 to 999 ms
BINARY INPUT 1 Adjustable threshold and hysteresis
Timer
Range Inaccuracy
0 – 50 ms ≤ 1 ms
50 – 500 ms ≤ 2 ms
> 500 ms ≤ 1%
Resolution 1 ms
Voltmeter
Measurement method: AC true RMS, DC mean value
Insulation 900 V, 1273 Vpeak
Input rating 900 V
Inaccuracy
Ranges DC
0-1 V ±0.5% of reading + 3 mV
0-10 V ±0.5% of reading + 7 mV
0-100 V ±0.5% of reading + 30 mV
0-900 V ±0.5% of reading + 300 mV

Ada masalah dengan produk ini?

ULASAN PEMBELI

Toped Illustration

Belum ada ulasan untuk produk ini

Beli produk ini dan jadilah yang pertama memberikan ulasan