Generator Spare Parts Alternator AVR R731 Automatic Voltage Regulator
ELECTRICAL SCHEMATICS 2 typical wiring schematics are provided : - with the CT for parallel operation on the phase U - with the CT for parallel operation on the phase V
Input voltage : - High voltage tap (400V) : 340V-5% to 480V=5% - Medium voltage tap (230V) : 200V-5% to 240V+5% - Low voltage tap (110V) : 90V-5% to 140V+5%
Internal voltage rheostat : The voltage can be adjusted using the internal rheostat P1. This rheostat is designed to provide +/-5% adjustment from any voltage within the above voltage ranges.
Remote voltage rheostat : If required, remove the ST10 jumper in order to connect a remote voltage rheostat. A 470 Ohms - 3W rheostat can be used for a +/-5% voltage adjustment range or a 1k Ohms - 3W rheostat for a +/-10% voltage range. An ST1 jumper was included on older R731 modules to increase the voltage adjustment range but was discontinued. voltage droop Current sensing : C.T. for // operation Location : standard line 1 (U), option line 2 (V). - Maximum continuous current : 1.3A - Nominal current : 1A - Maximum current for 10s : 10A
Voltage droop rheostat : The P2 rheostat on the R731 can be used to adjust the voltage droop. It is designed to provide a minimum voltage droop of 8% at 0 power factor and 1A from the paralleling CT.