Main Range of product : HDB3wLE Product or component type : Residual current breaker with overcurrent protection (RCBO) Mechanical durability : 25000 cycles Electrical durability : 6000 cycles Suitability for isolation : Yes Trip unit technology : Thermal-magnetic Device application : Isolation Control
Complementary Poles description : 1P + N [In] rated current : 10.0 A Reset : - Manual reset earth leakage - Manual reset overcurrent [Ue] rated operational voltage : 230 V AC 50...60 Hz Input overvoltage protection : 280 V +/- 5 % AC Residual current : 30.0 mA [Uimp] rated impulse withstand voltage : 4.0 kV Curve code : C Magnetic tripping limit : 5...10 x In Breaking capacity : 6.0 kA [Ui] rated insulation voltage : 500.0 V between phases Protection type : - Short-circuit protection - Overload protection - Earth-leakage protection - Residual current breaker with overcurrent protection (RCBO) Mounting support : 35 mm DIN rail Clamping connection capacity : <= 16 mm² Tightening torque : 2.5 N.m Provision for padlocking : Handle padlockable in on and off position Connections - terminals : Forked type tag connectors Height : 94 mm Width : 44.5 mm Depth : 74.5 mm
Environment Environmental characteristic : - High temperature: category 2 28 cycles conforming to IEC 60068-2 - Humidity resistant: category 2 28 cycles conforming to IEC 60068-2 Dielectric test voltage : 2.0 kV 50...60 Hz 1 min Shock resistance : 30 gn (duration = 11.0 ms) for 3 shocks IP degree of protection : IP20 Pollution degree : 2 Electrical shock protection class : Class II Ambient air temperature for operation : -20…60 °C Ambient air temperature for storage : -40…70 °C Standards : IEC 61009-1 Product certifications : CE Sensitivity : 30 mA