KEW 6315-03 | Power Quality Analyzer KYORITSU
Specifications
Wiring connections : 1P2W, 1P3W, 3P3W, 3P4W
Measurements and parameters : Voltage, Current, Frequency, Active power, Reactive power, Apparent power,Active energy, Reactive energy, Apparent energy, Power factor (cos ),Neutral current, Demand, Harmonics, Quality (Swell/Dip/Interruption, Transients/Over voltage, Inrush current, Unbalance rate), Capacitance calculation for PF correction unit, Flicker
Voltage (RMS)
Range : 600.0/1000V
Accuracy : 0.2%rdg0.2%f.s. (sine wave, 40 - 70Hz)
Allowable input : 1 - 120% of each range (rms). 200% of each range (peak)
Display range : 0.15 - 130% of each range
Crest factor : 3 or less
Sampling speed of Voltage transient : 24s
Current (RMS) Range :
8128(50A type) : 5/50A/AUTO
8127(100A type) : 10/100A/AUTO
8126(200A type) : 20/200A/AUTO
8125(500A type) : 50/500A/AUTO
8124/8130(1000A type) : 100/1000A/AUTO
8146/8147/8148(10A type) : 1/10A/AUTO
8129(3000Atype) : 300/1000/3000
Applicable standards : IEC 61010-1 CAT IV 300V, CAT III 600V, CAT II 1000V Pollution degree 2; IEC 61010-2-030, IEC 61010-031, IEC 61326, EN 50160; IEC 61000-4-30 Class S, IEC 61000-4-15, IEC 61000-4-7
Power supply (AC Line) : AC100 - 240V / 50 - 60Hz / 7VA max
Power supply (DC battery) : Alcaline size AA battery LR6 or Ni-MH (HR-15-51) 6; Battery life approx. 3h (LR6, Backlight OFF)
Dimensions : 175(L) 120(W) 68(D) mm
Weight : Approx. 900g
Included Accessories : 7141B(Voltage test lead), 7170(Power cord), 7219(USB cable), 8326-02(SD card 2GB), 9135(Carrying case for KEW 6315-03), Input terminal plate 6, KEW Windows for KEW 6315 (software), Quick manual, Alkaline size AA battery (LR6) 6