Display type : Display type
Output type : Contact output (SPDT)
Pin type : 8-pin
Memory : Not provided
Supply voltage : 100 to 240 VAC, 12 to 48 VDC
Rated time : 0.1 to 999.9 s
Rated supply voltage : 100 to 240 VAC (50/60 Hz), 12 to 48 VDC (permissible ripple: 20% max.)
Operating voltage range : 85% to 110% of rated supply voltage
Power consumption :
- Approx. 12 VA at 240 VAC
- Approx. 2.5 W at 48 VDC
Mounting method : Surface mounting or flush mounting
Display : 7-segment LEDs (10-mm-high characters), UP indicator
Input method : Contact open and short-circuit input
Output mode : N mode (Power ON-delay)
Control outputs : SPDT: 3 A at 250 VAC, resistive load (cosφ = 1)
Ambient temperature :
- Operating:–10°C to 55°C (with no icing or condensation)
- Storage:–25°C to 65°C (with no icing or condensation)
Ambient humidity : Operating: 35% to 85%
Case color : Light gray (Munsell 5Y7/1)
Insulation resistance : 100 MΩ min. (at 500 VDC) (between current-carrying terminal and exposed non-current carrying metal parts, between power supply circuit and control output circuit)
Dielectric strength : 2,000 VAC, 50/60 Hz for 1 min (between current-carrying terminal and exposed non-current-carrying metal parts, between power supply circuit and control output circuit)
Impulse withstand voltage : 6 kV (between power supply terminal) & 6 kV (between current-carrying terminal and exposed non-current carrying metal parts)
Noise immunity : Square-wave noise by noise simulator
- AC: ±2 kV (between power supply terminals)
- DC: ±480 V (between power supply terminals), ±500 V (between input terminals)
Static immunity Malfunction : 8 kV
Vibration resistance :
- Destruction:10 to 55 Hz with 0.75-mm single amplitude each in 3 directions for 2 hours each
- Malfunction:10 to 55 Hz with 0.5-mm single amplitude each in 3 directions for 10 minutes each
Shock resistance :
- Destruction:300 m/s2 3 times each in 6 directions
- Malfunct