Number of I/O points : No expansion (Control unit only) 14 points Input : 8 Output : 6
Rated voltage 24 V DC Operating voltage range 20.4 to 28.8 V DC
Allowed momentary power off time 5 ms (at 20.4 V DC), 10 ms (21.6 V DC or higher) Operating temperature : 0 to +55 32 to +131 Storage temperature : -40 to +70 -40 to +158 (-20 to +70 -4 to +158 for T32 only) Operating humidity : 10 to 95% RH (at 25 77 , no condensation) Storage humidity : 10 to 95% RH (at 25 77 , no condensation)
Rated input voltage : 24 V DC Applied voltage range : 21.6 to 26.4 V DC Rated input current : 2.6 mA approx. (at 24 V DC) Input impedance : 9.1 k approx. Input points per common : 8 points / common Min. ON voltage/Min. ON current : 19.2 V / 2 mA Max. OFF voltage/Max. OFF current : 2.4 V / 1.2 mA Response time : OFFON : 20 s or less * An input time constant (0.1 to 64 ms) can be set. Response time : ONOFF : Same as above Insulation method :Photocoupler
Output type : 1a Rated control capacity : 2 A 250 V AC, 2 A 30 V DC (4.5 A / common) Response time : OFFON : 10 ms approx. Response time : ONOFF : 8 ms approx. Life time : Mechanical : 2 x 107 operations or more Life time : Electrical 105 operations or more Surge absorber : None Output points per common : 4 points / common + 1 point / common + 1point / comon