Size: DIN W48×H48mm Display method: 4-digit 7-segment LED Control method: ON/OFF control, P, PI, PD, PID control Input specification: Thermocouple: K(CA), J(IC), L(IC); RTD: DPt100Ω, Cu50Ω Sampling cycle: 100ms Control output: Relay (250VAC~ 3A) or SSR drive (12VDC ) [ON/OFF, phase, cycle] Option output: Alarm 1 Power supply: 100-240VAC~ 50/60Hz Display accuracy_RTD: •At room temperature(23ºC ± 5ºC):(PV ± 0.5% or ±1ºC, select the higher one) ± 1-digit •Out of room temperature range:(PV± 0.5% or ±2ºC, select the higher one)± 1-digit Display accuracy_Thermocouple: •At room temperature(23ºC ± 5ºC):(PV ± 0.5% or ±1ºC, select the higher one) ± 1-digit •Out of room temperature range:(PV± 0.5% or ±2ºC, select the higher one)± 1-digit Hysteresis(adjustable sensitivity): 1 to 100℃/℉(0.1 to 50.0℃/℉) variable Proportional band: 0.1 to 999.9℃/℉ Integral time: 0 to 9999 sec Derivative time: 0 to 9999 sec Control period: 0.5 to 120.0 sec Manual reset: 0.0 to 100.0% Environment_Ambient temperature: -10 to 50℃, storage: -20 to 60℃ Environment_Ambient humidity: 35 to 85% RH, storage: 35 to 85% RH
※In case of the AC voltage model, SSR drive output method (standard ON/OFF control, cycle, control, phase control) is available to select. ※Display accuracy: Thermocouple L(IC) type, RTD Cu50Ω •At room temperature (23℃ ±5℃): (PV ±0.5% or ±2℃, select the higher one) ±1-digit •Out of room temperature range: (PV ±0.5% or ±3℃, select the higher one) ±1digit In case of TC4SP Series, ±1℃ will be added. ※The weight includes packaging. The weight in parenthesis is for unit only. ※Environment resistance is rated at no freezing or condensation.