Display method: Non-display Measured range_Temperature: -19.9~60.0℃ Measured range_Humidity: 0.0 to 99.9%RH(recommended: 0.0 to 90.0%) Output_Temperature: Current output(DC4-20mA) Output_Humidity: Current output(DC4-20mA) Sampling cycle: 500ms Power supply: 24VDC Protection structure: IP10 Accuracy_Temperature: ±1.0℃(at room temperature) Accuracy_Humidity: ±3%RH(30 to 70%RH, at room temp.), ±4%RH(10 to 90%RH) Resolution: 1/1000 Environment_Ambient temperature: -20 to 60℃, storage: -20 to 60℃
※Accuracy: •Room temperature is 23℃±5℃. •It may cause degree of degradation when this unit is exposed to organic chemicals such as alcohol gas or sulfuric acid. •It may cause degree of degradation for humidity when using this unit at high temperature/humidity environment for a long time. • It may cause error of humidity value when this unit is exposed to high humidity environment (over 80%RH) for a long time. ※The weight includes packaging. The weight in parenthesis is for unit only. ※Environment resistance is rated at no freezing or condensation.